Thermodynamics

Heat Conduction Calculator

Calculate steady one-dimensional heat conduction rate, heat flux, conductivity, area, temperature difference, or thickness using Fourier's law.

Formula Q̇ = k A ΔT / LReviewed Sep 8, 2026

Heat conduction through a flat layer is commonly estimated with Fourier's law. This calculator covers two closely related plane-wall forms: total heat-transfer rate, Q̇ = k A ΔT / L, and heat flux, q'' = k ΔT / L. Use Heat Rate mode when total wall area matters and you want the overall watts crossing the wall. Use Heat Flux mode when you want watts per unit area through the material itself.

Calculation Bench
Calculation Mode
Solve for
01

k · Material property describing how readily heat conducts through the wall.

02

A · Cross-sectional area normal to the heat-flow direction.

03

ΔT · Magnitude of the temperature drop across the conduction path.

04

L · Length of the conduction path through the layer.

Plane-wall, steady one-dimensional conduction only. If you need resistance-form results directly, use the Thermal Resistance Calculator instead.

Solution

Enter the required values to calculate heat transfer rate.

Q̇ = k A ΔT / L

Formula Sheet

Q˙=kAΔTL\dot{Q} = \dfrac{kA\Delta T}{L}
k=Q˙LAΔTk = \dfrac{\dot{Q}L}{A\Delta T}
A=Q˙LkΔTA = \dfrac{\dot{Q}L}{k\Delta T}
ΔT=Q˙LkA\Delta T = \dfrac{\dot{Q}L}{kA}
L=kAΔTQ˙L = \dfrac{kA\Delta T}{\dot{Q}}
q′′=kΔTLq'' = \dfrac{k\Delta T}{L}
k=q′′LΔTk = \dfrac{q''L}{\Delta T}
ΔT=q′′Lk\Delta T = \dfrac{q''L}{k}
L=kΔTq′′L = \dfrac{k\Delta T}{q''}
  • Q̇Heat Transfer Rate
  • q''Heat Flux
  • kThermal Conductivity
  • AArea
  • ΔTTemperature Difference
  • LWall Thickness

Variables & Units

SymbolVariableDescriptionCommon Units
Q̇Heat Transfer RateTotal steady heat-flow rate through the full wall area.W, kW, Btu/h
q''Heat FluxHeat-transfer rate per unit area through the wall.W/m², kW/m², W/cm², Btu/(h·ft²)
kThermal ConductivityMaterial property describing how readily heat conducts through the wall.W/(m·K), Btu/(h·ft·°F)
AAreaCross-sectional area normal to the heat-flow direction.cm², m², in², ft²
ΔTTemperature DifferenceMagnitude of the temperature drop across the conduction path.K, °C, °F
LWall ThicknessLength of the conduction path through the layer.mm, cm, m, in

How to Use This Calculator

  • 01Choose the calculation mode first. Use Heat Rate for total watts through the wall, or Heat Flux for watts per unit area.
  • 02Select which variable to solve for. The calculator then shows only the inputs needed for that form of Fourier's law.
  • 03Enter positive magnitudes for conductivity, area, temperature difference, thickness, heat-transfer rate, and heat flux. This page does not track sign direction with the negative sign from differential Fourier's law.
  • 04Use a temperature difference, not an absolute temperature. A change of 20 °C equals a change of 20 K for conduction calculations. Use the material table as a starting point, then replace it with manufacturer data for final work.

How the Formula Works

For a steady one-dimensional plane wall with uniform area and constant thermal conductivity, Fourier's law reduces to Q̇ = k A ΔT / L. Heat transfer increases when conductivity, area, or temperature difference increases, and it decreases when the conduction path gets thicker.

Heat flux is the heat-transfer rate per unit area: q'' = Q̇ / A = k ΔT / L. That makes Heat Flux mode useful when you want a wall-performance quantity independent of panel size, while Heat Rate mode is the better choice when total wall area is part of the design problem.

Worked Example 01

Heat transfer rate through insulation

Known

  • Thermal Conductivity (k): 0.04 W/(m·K)
  • Area (A): 10 m²
  • Temperature Difference (ΔT): 25 K
  • Wall Thickness (L): 0.1 m

Formula

Q̇ = k A ΔT / L

Substitution

Q̇ = 0.04 × 10 × 25 / 0.1

Result

Q̇ = 100 W

A 100 mm insulation layer over 10 m² with a 25 K temperature drop conducts 100 W in this steady plane-wall approximation.

Worked Example 02

Required thickness for a target heat leak

Known

  • Heat Transfer Rate (Q̇): 100 W
  • Thermal Conductivity (k): 0.04 W/(m·K)
  • Area (A): 10 m²
  • Temperature Difference (ΔT): 25 K

Formula

L = k A ΔT / Q̇

Substitution

L = 0.04 × 10 × 25 / 100

Result

L = 0.1 m

To limit the steady conduction rate to 100 W under those conditions, the required thickness is 0.1 m.

Worked Example 03

Heat flux through a thin layer

Known

  • Thermal Conductivity (k): 0.5 W/(m·K)
  • Temperature Difference (ΔT): 40 K
  • Wall Thickness (L): 0.02 m

Formula

q'' = k ΔT / L

Substitution

q'' = 0.5 × 40 / 0.02

Result

q'' = 1000 W/m²

This wall conducts 1000 W of heat per square meter under the given steady one-dimensional conditions.

Worked Example 04

Back-solve thermal conductivity from measured heat flux

Known

  • Heat Flux (q''): 1000 W/m²
  • Temperature Difference (ΔT): 40 K
  • Wall Thickness (L): 0.02 m

Formula

k = q'' L / ΔT

Substitution

k = 1000 × 0.02 / 40

Result

k = 0.5 W/(m·K)

Measured heat-flux data can be rearranged to estimate conductivity when the thickness and temperature drop are known.

Applications

  • 01Estimating watts conducted through insulation, panels, plates, and building layers
  • 02Checking heat flux through walls, liners, and flat thermal barriers
  • 03Back-solving required thickness, conductivity, or allowable temperature drop in preliminary thermal design
  • 04Screening whether insulation thickness changes have a meaningful effect before doing a full U-value or heat-loss calculation

Representative Thermal Conductivities

MaterialThermal ConductivityUse note
Copper390 W/(m·K)High-conductivity metal; verify alloy and temperature.
Aluminum200 W/(m·K)Common heat-spreader material.
Steel50 W/(m·K)Varies significantly by grade.
Water0.6 W/(m·K)Conduction only; moving water also convects.
Brick0.4-0.5 W/(m·K)Representative masonry range.
Wood0.2 W/(m·K)Strongly depends on species and moisture.
Cork0.04 W/(m·K)Insulation-like material.
Air0.026 W/(m·K)Still air only; gaps can include convection.

Assumptions

  • 01The wall is modeled as steady, one-dimensional conduction through a uniform flat layer.
  • 02Thermal conductivity is treated as constant over the temperature range.
  • 03The page works with positive magnitudes and does not represent directional sign with the negative gradient form.

Where This Model Stops

  • 01Does not model cylindrical or spherical conduction, fins, contact resistance, internal heat generation, or multidimensional heat spreading.
  • 02Does not include convection or radiation boundary resistances unless you convert the problem into an equivalent conduction-only screening estimate.
  • 03Use the Thermal Resistance Calculator if you want resistance-form results directly rather than Fourier-law heat rate or heat flux.
  • 04Does not model pipes or cylinders directly; for pipe insulation, use a cylindrical conduction method rather than treating the pipe wall as a flat slab.

References

  1. [1]
    16.2 Introduction to Conduction

    MIT Unified Engineering Notes

    States the plane-wall Fourier-law forms for total heat-transfer rate and heat flux, and defines thermal conductivity and heat flux units.

  2. [2]
    16.3 Steady-State One-Dimensional Conduction

    MIT Unified Engineering Notes

    Develops the steady one-dimensional conduction model and applies it to a plane slab.

  3. [3]
    NIST Guide to the SI, Appendix B.9

    National Institute of Standards and Technology

    Provides official conversion factors for heat flow rate, heat-flux-related energy-per-area-time units, and thermal conductivity.

Frequently Asked Questions

What is the difference between heat transfer rate and heat flux?

Heat transfer rate Q̇ is the total watts crossing the whole wall, while heat flux q'' is watts per unit area. They are related by q'' = Q̇/A.

How is this different from the Thermal Resistance Calculator?

This page is centered on Fourier's law and explicitly exposes heat flux as well as total heat rate. The Thermal Resistance Calculator expresses the same plane-wall physics in resistance form R = L/(kA) and is better when you want resistance directly.

Can I use Celsius for the temperature difference?

Yes. For temperature differences, 1 °C change equals 1 K change, so either is fine. Fahrenheit differences are larger units and are converted appropriately by the calculator.

Can I use this for pipe insulation?

Only as a rough screening estimate for thin, nearly flat sections. Cylindrical conduction uses a logarithmic radius term, so a pipe-wall or pipe-insulation design should use a cylindrical conduction method when accuracy matters.